Two percentage margins added to the room loads before the coil calculation. They apply on every calculation method.

Each margin has a tick box and a value. When the box is off the margin is left out of the calculation; a value of 0 % with the box on has the same effect on the result.
On screen: Sensible (sensible safety margin).
Adds a percentage to the room's sensible (temperature) load, after the supply-side allowances have been applied. It does not touch the fresh-air load.
| Setting | Value |
|---|---|
| Default | On, 10 % |
| Allowed | 0 to 100 % |
RSH = room sensible × (1 + supply-side allowances ÷ 100) × (1 + sensible safety ÷ 100)
RSH, the room sensible heat, is the first step of the coil chain; see Coil and duct allowances.
On screen: Latent (latent safety margin).
Adds a percentage to the room's latent (moisture) load in the same way. It does not touch the fresh-air load either.
| Setting | Value |
|---|---|
| Default | On, 5 % |
| Allowed | 0 to 100 % |
RLH = room latent × (1 + supply duct leakage ÷ 100) × (1 + latent safety ÷ 100)
The fresh-air load is added afterwards, without a margin, in the coil chain; see Coil and duct allowances.