Design margins

Two percentage margins added to the room loads before the coil calculation. They apply on every calculation method.

Design margins

Each margin has a tick box and a value. When the box is off the margin is left out of the calculation; a value of 0 % with the box on has the same effect on the result.

Sensible

On screen: Sensible (sensible safety margin).

Adds a percentage to the room's sensible (temperature) load, after the supply-side allowances have been applied. It does not touch the fresh-air load.

Setting Value
Default On, 10 %
Allowed 0 to 100 %

RSH = room sensible × (1 + supply-side allowances ÷ 100) × (1 + sensible safety ÷ 100)

RSH, the room sensible heat, is the first step of the coil chain; see Coil and duct allowances.

Latent

On screen: Latent (latent safety margin).

Adds a percentage to the room's latent (moisture) load in the same way. It does not touch the fresh-air load either.

Setting Value
Default On, 5 %
Allowed 0 to 100 %

RLH = room latent × (1 + supply duct leakage ÷ 100) × (1 + latent safety ÷ 100)

The fresh-air load is added afterwards, without a margin, in the coil chain; see Coil and duct allowances.